SMC 2350/2360 Telecom Gas Monitors

Continuously monitors for carbon monoxide gas leaks in utility enclosures.

The SMC 2350/2360 Telecom Gas Monitors both continuously monitor for the presence of Carbon Monoxide (CO), but the Model 2360 also monitors for combustible gases. These hazardous gases are monitored in confined spaces in telecom sites, such as utility enclosures, to reduce the hazard of gas explosion and to maintain personnel safety.

  • Solid State Semiconductor Technology:
    • detects low points-per-million (ppm) levels of hazardous gas
    • maintains the life cycle of the product for long periods
    • easy maintenance
  • Operate on -48 VDC power, typically used in telecom applications
  • 68 dB audible alarm along with visual indication
Input Power
  • 2350
    • -48V
  • 2360
    • -48V
Alarm Calibration Range
  • 2350
    • Carbon Monoxide: 100-200 ppm
  • 2360
    • Combustible Gas (Methane): 2,500-12,500 ppm
    • Carbon Monoxide: 100-200 ppm
Response Time
  • 2350
    • Less than 30 seconds
  • 2360
    • Less than 30 seconds
Operating Temperature Range
  • 2350
    • 32 o to 104oF (0 to 40oC)
  • 2360
    • 32 o to 104oF (0 to 40oC)
Output Relay Rating
  • 2350
    • Four SPDT 6 Amp non-inducting
  • 2360
    • Four SPDT 6 Amp non-inducting
Audible Alarm
  • 2350
    • 68 dB at 2900 Hz
  • 2360
    • 68 dB at 2900 Hz
Size
  • 2350
    • 4.5 x 8.9 x 1.6 in. (11.4 x 22.5 x 4.1 cm)
  • 2360
    • 4.5 x 8.9 x 1.6 in. (11.4 x 22.5 x 4.1 cm)
Weight
  • 2350
    • 3 lb. (1.3 Kg)
  • 2360
    • 3 lb. (1.3 Kg) 